<DS23>
<1> Smart Manager main/sub selection
OFF: Main
ON: Sub
Normally, this bit is set to OFF.
When two Smart Manager units are used as a main unit and a sub unit
with the same mode setting, set this bit to OFF (Main) for one unit and to
ON (Sub) for the other unit.
<2> to <5> Control group selection
Control group selection
All groups
Group 1 ~ 16
Group 17 ~ 32
Group 33 ~ 48
Group 49 ~ 64
These bits specify a group range used in the control group selection.
The Smart Manager for which control group selection is set controls
only groups within the set group range.
To use the control group selection, set DS23-<2> to <5> and DS24-<5>
to <6>. For details, see "7.Mode Setting for Smart Manager".
<6> Central control/remote controller mode selection
OFF: Central control mode
ON: Remote controller mode
Central control mode:
Remote controller mode: The smart manager is used as the remote
<7> Central control Main/Sub selection
OFF: Main
ON: Sub
This setting is required when multiple Smart Manager units are used or
another central control unit is used.
(1) Set this bit to OFF when one Smart Manager unit is used.
(2) When multiple central control units are used as a main unit and sub
units, set to OFF (Main) for one unit and set to ON (Sub) for other
units.
AMP Air Conditioning
DS24-<6>
OFF
ON
ON
ON
ON
The smart manager is used as the central
control device.
controller.
ON
OFF
DS23
-
<2> ON
<3> ON
<4> ON
<5> ON
<8> Central button enable/
disable
OFF:
ON:
* The
the remote controller mode
regardless of this setting.
www.ampair.co.uk | sales@ampair.co.uk
Installation Manual
Factory setting: All OFF
DS23
1
2 3 4 5 6 7 8
button operation is
permitted
button operation is
inhibited
button is disabled in
EN
-EN
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smart manager

Table of Contents