Omron POWLI Instruction Manual page 31

Table of Contents

Advertisement

2
. Installation and Connection
2-3-2 Connecting a device to the power supply output (BU3002SWG)
(1) Connect devices that require backup to the unit's power supply output receptacle or output
terminal block.
Make sure that the total capacity of the devices connected to the output receptacle does
not exceed the output rated capacity of the BU3002SWG. If the overload indication (
displayed, reduce the number of connected devices.
BU3002SWG (Rated value of output capacity: Max. 3kVA/2100W)
"Power supply output" group
Group A
Group B
Group C
• Procedure for connection
to power supply output receptacle (IEC60320
C13)
Connect it directly.
18
Output receptacle
C19: 1 (Rated capacity: 20A)
C13: 1 (Rated capacity: 15A)
C13: 2 (Rated capacity: 15A)
C13: 2 (Rated capacity: 15A)
Group A
Group B
Group C
Group A
Group B
Plug of connected device
Output terminal block
1 line (Rated capacity: 20A)
1 line (Rated capacity: 20A)
Group control of power supply output
See also
See Page 13
• Procedure for connection
to power supply output receptacle (IEC60320
C19)
Connect it directly.
Plug of connected device
) is