. Using the UPS monitoring software and contact signal
■ Setting Switch
l Function settings using the setting switch
The function of this setting switch varies depending on the UPS equipped with the SC08G.
For details, refer to the "Items that can be set using the contact signal card" in the instruction manual of
the UPS equipped with the SC08G.
(Note 1: All setting switches are set to OFF when shipped from the factory.)
(Note 2: Always set the setting switch 3 to "OFF". Also, set the setting switch not described in the UPS
instruction manual to "OFF".)
4-4 Signal I/O Connector (Female DSUB 9P)
Pin assignment
5  4  3  2  1
9  8  7  6
Front view
Screw size: inch screw thread
#4-40 UNC
4-5 Remote ON/OFF connector
Pin assignment
1
2
Front view
Screw size: inch screw thread
#4-40 UNC
Use a wire that conforms to Table 1 when using
the remote ON/OFF connector.
4-6 Signal I/O Rating
l Signal Output (BU, BU, BL, BL, TR, TR, WB, WB)
Relay rating
Applicable voltage: 30 VDC or less
Maximum current: 2A (under resistive load)
l Backup Power Supply Stop Signal Input (BS,BS)
Input voltage
HIGH (ON)
LOW(OFF)
High Sink current at signal input
l Remote ON/OFF
Voltage between terminals: 5 VDC
Current when closed: max.10 mA
72
Pin number
1
Backup Signal output-1 (BU-1)
2
Backup Signal output-2 (BU-2)
3
Battery Low signal output-1 (BL-1)
4
Battery Low signal output-1 (BL-2)
5
Trouble signal output (TR)
6
COMMON (TR/WB-COM) of TR and WB signals
7
Battery Replacement Signal output (WB)
8
Backup stop signal input+ (BS+)
9
Backup stop signal input- (BS-)
Pin number
1
2
1A (under inductive load)
8 to 24 VDC (at the setting of 24 VDC)
5 to 12 VDC (at the setting of 12 VDC)
0.7 VDC or less
max. 20mA
Signal name
Signal name
Remote ON/OFF (+)
Remote ON/OFF (-)
Recommended cable size AWG 14 to 28
Amount of stripped wire
Table 1
6 to 7mm

Advertisement