. Installation and Connection
2. Power supply output group B, C
The output start times for power supply output group B and C are independent of power supply out-
put group A, so they can be delayed or set to precede the output stop time.
The output start/stop time control funtion is available when using the included "PowerAct Pro" UPS
monitoring software, "UPS Power Manager" or "SNMP/Web card".
Output ON/OFF can be controlled with the included UPS monitoring software while the BU1002SWG is
operating.
The delay settings and ON/OFF control described here can be performed independently for power
supply output group B and power supply output group C.
This function can be used to set the startup order of servers, peripheral devices, etc.
The output receptacles can also be forcibly turned ON/OFF remotely.
Power supply output group A
Power supply output group B
Power supply output group C
* In the factory setting, the time is set to 0 second.
2-3-1 Connecting a device to the power supply output (BU1002SWG)
(1) Connect devices that require backup to the unit's power supply output receptacle or output terminal
block.
Make sure that the total capacity of the devices connected to the output receptacle does
not exceed the output rated capacity of the BU1002SWG. If the overload indication (
displayed, reduce the number of connected devices.
BU1002SWG (Rated value of output capacity: Max. 1kVA/700W)
"Power supply output" group
Group A
Group B
Group C
USB
RS232C
OPTION SLOT
COOLING FAN
AC INPUT
OVER CURRENT
PROTECTION 10A
GND
Uninterruptible Power Supply
MODEL : BU1002SWG
Rated Voltage: AC220-240V
Max. Current: 5.8A Rated Freq.:50/60Hz
G
OMRON Corporation
MADE IN TAIWAN
INPUT AC220-240V
50/60Hz 5.8A 1φ3W
Group C
14
Output ON
Time setting
Time setting
Output receptacle
C13: 1 (Rated capacity: 15A)
C13: 1 (Rated capacity: 15A)
C13: 1 (Rated capacity: 15A)
OUTPUT
AC220-240V
50/60Hz 4.6A Max 1φ3W
OUPUT POWER
1kVA / 700W Max.
A
Group A
Group C
C
B
Group B
L2C
L2B
L1C
L1B
B
C
Group B
Output terminal block
1 line (Rated capacity: 20A)
1 line (Rated capacity: 20A)
Group control of power supply output
See also
See Page 13
Output OFF
Time setting
Time setting
) is

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bu3002swgBu1002swg

Table of Contents