Parameter #
Fuel 0
Fuel 1
Parameter Name
Gas Oil Gas Oil
601
-
Reference Point**
-
608
602
-
Rotation Direction**
-
609
606
-
Position Tolerance
-
610
611
-
Reference Type
-
612
SCC Inc.
LEGEND - Password Access: U = User, S = Service, O = OEM, U/S = View - User, Write - Service, S/O = View - Service, Write - OEM
Shaded Parameters = Frequently Used. ** Parameters = Must Set. Fuel 1 parameters for LMV36 only.
U/S/O
Default
Range
600 Level: Actuator and VSD Configuration
601:00 = 1
0-1
601:01 = 0
1
0-1
602:00 = 0
0-1
602:01 = 0
0
0-1
S/O
606:00 = 1.7°
0.5-4.0°
606:01 = 1.7°
1.7°
0.0-4.0°
611:00 = 0
0-3
611:01 = 0
0
0-3
Determines the reference point of the SQM33 actuators. The actuators will reference after a normal
shutdown, lockout, or loss of power to the LMV3. In order to reference, the actuators must drive outside of
their 0-90° operating range. This parameter sets whether the actuators will reference closed (<0°) or open
(>90°).
Index 00 = fuel actuator. Index 01 = air actuator
0 = closed (<0°)
1 = open (>90°)
Note: The reference point of the air actuator can only be set under parameter 601 and is not displayed
under parameter 608.
Determines the direction of rotation of the SQM33 actuators. The descriptions of the rotation are valid
when the actuator shaft is pointed at your eye.
Index 00 = fuel actuator. Index 01 = air actuator
0 = counterclockwise
1 = clockwise
Note: The direction of rotation of the air actuator can only be set under parameter 602 and is not
displayed under parameter 609.
Determines the allowed tolerance on the position of the actuators. If the actuator's position differs by
greater than this amount from the expected position, a lockout occurs. The default setting of 1.7° is
recommended.
Index 00 = fuel actuator. Index 01 = air actuator
Note: The allowed tolerance of the air actuator can only be set under parameter 606 and is not displayed
under parameter 610.
Determines the type of reference of the actuators. These settings should be left at the default values of 0.
Index 00 = fuel actuator. Index 01 = air actuator
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1... actuators only)
3 = both
Note: The type of reference of the air actuator can only be set under parameter 611 and is not displayed
under parameter 612.