LMV Series
Terminal
Type
X24‐06.1
PE
X24‐06.2
Neutral
X24‐06.3
Output
X31‐01.1
Input
X31‐01.2
PE
X31‐01.3
Neutral
X31‐01.4
Line
X31‐02.1
X31‐02.2
Output
X32‐01.1
X32‐01.2
Input
X32‐01.3
X32‐01.4
Output
X32‐01.5
Input
X32‐02.1
Output
X32‐02.2
Input
X54
Actuator
X54a.1
X54a.2
X54a.3
Fuel 1 ‐ Fuel
actuator
X54a.4
X54a.5
X54a.6
X54b.1
X54b.2
X54b.3
Fuel 0 ‐ Fuel
actuator
X54b.4
X54b.5
X54b.6
SCC Inc.
AGM60 Terminals
Function
Protective Earth ground
Neutral
Outside main safety valve
Typical: atomizing air compressor or gas
booster (fuel 0)
Fuel select
De‐energized = fuel 0
Energized = fuel 1
Protective Earth ground
Neutral
Line, fused
Fuel select fuel 0
Fuel select fuel 1
Gas trains: High gas PS ‐or‐ POC ‐or‐
valve proving pressure switch
Oil trains: High oil PS ‐or‐ POC (common)
Main fuel valve V1 (upstream ‐ common)
Main fuel valve V2 (downstream ‐ common)
Valve proving pressure switch ‐or‐
low oil pressure switch (common)
Outside main safety valve
Typical: atomizing air compressor or gas
booster (common)
Burner switch
Connect cable AGV61.100
Power
Ground
Output channel A
Output channel B
Input channel A
Input channel B
Power
Ground
Output channel A
Output channel B
Input channel A
Input channel B
Page 11
Technical Instructions
Document No. LV3‐1000
Rating
N/A
1.6A, 120VAC
1.5mA, 120VAC
N/A
500mA, 120VAC
Max. 10mA
1.5mA, 120VAC
1.6A, 120VAC
1.5mA, 120VAC
1.6A, 120VAC
1.5mA, 120VAC
N/A
Section 2