Siemens LMV3 series Technical Instructions page 156

Hide thumbs Also See for LMV3 series:
Table of Contents

Advertisement

Error
Diag.
Code
Code
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
Any #
Manual locking
1
Manual locking by contact
2
Manual locking by AZL23
3
Manual locking by PC software
8
Manual locking by AZL23 - timeout / communication breakdown
167
9
Manual locking by PC software - communication breakdown
33
Manual locking by PC software - test of lockout
168
Any #
Internal error management
169
Any #
Internal error management
170
Any #
Internal error management
171
Any #
Internal error management
200
Any #
System error-free
OFF
Any #
Prevention of startup
1
No operating mode selected
201
2
No fuel train defined
OFF UPr0
4
No curves defined
OFF Upr1
8
Standardized speed undefined
16
Backup / restore was not possible
202
Any #
Internal error operating mode selection
203
Any #
Internal error
24
Program stop is active (phase 24)
36
Program stop is active (phase 36)
204
44
Program stop is active (phase 44)
52
Program stop is active (phase 52)
205
Any #
Internal error
Section 6
Meaning for the LMV3 System
The LMV3 has been manually locked (no fault). Reset the LMV3 to clear
the fault.
During a curve adjustment on the AZL23, the timeout for menu operation
has elapsed (parameter 127), or communication between the LMV3 and
AZL23 has been lost. Re-establish communication and reset the fault.
During a curve adjustment on the ACS410 software, communication
between the LMV3 and the ACS410 software has been lost for more than
30 seconds. Re-establish communication and reset the fault.
A reset was made via the ACS410 software when the LMV3 was not in
alarm. Reset the LMV3 to clear the fault.
If the fault occurs continuously, replace the LMV3.
If the fault occurs continuously, replace the LMV3.
The LMV3 displays this code when there are no current faults.
The LMV3 cannot startup because a parameter is not defined. The
diagnostic code calls out which parameter is not defined. Choose a valid
selection for the undefined parameter and then reset the fault.
Make a valid selection of parameter 201/301, then reset the fault.
Make a valid selection of parameter 201/301, then reset the fault. If the
fault occurs continuously, replace the LMV3.
No fault: The program stop feature is active. Set parameter 208 to 0 to
deactivate the program stop if it is no longer required.
If the fault occurs continuously, replace the LMV3.
Page 22
Corrective Action