Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
Any #
Internal error - backup / restore
157 (-99) Restore - ok, but backup < data set of current system
239 (-17) Backup - storage of backup in AZL23 faulty
240 (-16) Restore - no backup in AZL23
241 (-15) Restore - abortion due to unsuitable product no. (ASN)
242 (-14) Backup - backup made is inconsistent
243 (-13) Backup - data comparison between µCs faulty
244 (-12) Backup data are incompatible
245 (-11) Access error to parameter Restore_Complete
246 (-10) Restore - timeout when storing in EEPROM
137
247 (-9) Data received are inconsistent
248 (-8) Restore cannot at present be made
249 (-7) Restore - abortion due to unsuitable burner identification
250 (-6) Backup - CRC of one page is not correct
251 (-5) Backup - burner identification is not defined
252 (-4) After restore, pages still on ABORT
253 (-3) Restore cannot at present be made
254 (-2) Abortion due to transmission error
255 (-1) Abortion due to timeout during backup / restore
Section 6
Meaning for the LMV3 System
An error occurred while attempting to perform a backup or restore via
parameter 050. See diagnostic codes for more information.
No fault: Restore was successful, but the backup data record is smaller
than in the current system.
Reset the fault and repeat the backup.
There is no parameter set stored in the AZL23, so the restore process could
not be completed. Reset the fault.
The parameter set stored in the AZL23 has an unsuitable product no.
(ASN), so the restore process was aborted. Reset the fault.
The backed up parameter set is faulty and cannot be transferred back to
the LMV3. Reset the fault.
Reset the fault and repeat the backup.
The parameter set stored in the AZL23 is not compatible with the LMV3
software version, so the restore could not be completed. Reset the fault.
Reset the fault and repeat the restore.
Reset the fault and repeat the restore.
Some data in the parameter set stored in the AZL23 is invalid, so the
restore could not be completed. Reset the fault.
Reset the fault and repeat the restore.
The parameter set stored in the AZL23 has an unsuitable burner
identification and must not be transferred to the LMV3. Reset the fault
and do not attempt the restore again.
The restore was not possible because the backup data record is invalid.
Reset the fault.
A valid burner ID (parameter 113) is required to perform a backup. Set the
burner ID, reset the fault, and start the backup again.
Reset the fault and repeat the restore.
Reset the fault and repeat the restore.
Reset the fault and repeat the restore.
Communication between the LMV3 and AZL23 was interrupted during the
backup or restore. Re-establish communication and reset the fault. If the
fault continues, it is possible the AZL23 is too old and does not support the
backup / restore functions. If this is the case, replace the AZL23.
Page 19