Siemens LMV3 series Technical Instructions page 36

Hide thumbs Also See for LMV3 series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV3‐1000 
 
Terminal 
Type 
X74.1 
Fixed Input 
X74.2 
Programmable 
X74.3 
Output 
Programmable 
X74.4 
Input 
X74.5 
Fixed Output 
Programmable 
X75.1 
Input 
X75.2 
Fixed Output 
X92 
Modbus 
 
Section 2 
                                                          Page 8                                                                         SCC Inc. 
 
 
LMV3 Terminals 
Function 
24VDC power supply (+) 
24VDC power supply (‐) and 
speed sensor reference 
ground 
0/2‐10 VDC output for VSD 
speed ‐or‐ load 
Speed sensor pulse input 
Speed sensor power supply 
Fuel meter pulse input, low 0‐
1.5VDC, high 3‐10 VDC 
Fuel meter pulse power 
supply 
Modbus communications 
port for use with OCI412.10 
module  
 
Parameter 
Not configurable 
645 ‐ Analog out config 
542 ‐ VSD activation 
641 ‐ VSD standardization 
643 ‐ Type speed feedback 
644 ‐ Feedback pulse / rev 
662 ‐ VSD neutral zone 
663 ‐ VSD near zone 
Not configurable 
128/129 ‐ Fuel meter scale 
141 ‐ Modbus activation 
145 ‐ Modbus address 
146 ‐ Baud rate 
147 ‐ Parity 
LMV Series 
Rating 
24VDC 
N/A 
0/2‐10 VDC 
0‐10VDC 
15mA, 
10VDC 
0‐24 VDC, 
0.1‐300 Hz 
24VDC, 
15mA max 
N/A 
 

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents