Sensaphone 1104 User Manual page 96

Sensaphone telephone
Hide thumbs Also See for 1104:
Table of Contents

Advertisement

Communications / Dial-out:
Problem
1. The Model 1104 fails to dial out.
Cause
a)
The telephone number may be incorrectly
programmed.
b)
Tone or pulse (the current dialing
method) is not compatible with the
telephone line on which the Model 1104
is installed.
c)
Recognition Time is too long. An alert
condition does not remain in effect long
enough to become a valid alarm.
d)
Max Calls is set to zero.
Solution
Recheck programming steps.
Refer to Chapter 4, Section 4.2.1.
Switch from the current setting: from tone to
pulse, or from pulse to tone.
Refer to Chapter 4, Section 4.3.
Reprogram Recognition Time. Set the
Recognition Time to the minimum duration
required to create a valid alarm. If possible,
test the new setting by deliberately creating an
alert condition.
Refer to Chapter 5, Section 5.3.
Reprogram Max Calls. It is a good idea to set
your Max Calls to at least equal the number of
dial-out telephone numbers programmed.
Refer to Chapter 4, Section 4.12.1.

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Sensaphone 1104

Table of Contents