5.6.1 Programming Temperature Calibration

1. Press SET.
SET
#
2. Press CALIBRATE.
6
CALIBRATE
3. Press the number (1 to 4) of the selected temperature input to
be calibrated.
1
CALL
DELAY
4
MAX CALLS
4. Enter the number required to offset the current temperature
reading so a correct reading is obtained.
• To program a positive offset number (up to +10 degrees),
enter the number on the keypad. The Model 1104 recites the
digits as they are pressed.
• To program a negative offset number (up to –10 degrees),
first press PAUSE. The unit responds with a "beep. " Next,
enter the number on the keypad. The unit recites the digits as
they are pressed.
5. Press ENTER. The Model 1104 responds:"Enter. "
ENTER
ENTER
TONE
TONE
PM
PM
If you find that your calibration offset exceeds more
than + 5 or –5 degrees, other complicating factors
could be affecting normal operation of the Model
1104. Call Phonetics for technical assistance.

5.6.2 Interrogating Temperature Calibration

1. Press WHAT IS.
WHAT
IS
*
2. Press CALIBRATE.
72
2
3
VOICE
INTERCALL
TIME
REPS
NOTE