Recall Factory Trim-Sensor Trim; Analog Output Trim - Emerson Rosemount 3051S Series Reference Manual

Scalable pressure, flow, and level solution with hart protocol
Hide thumbs Also See for Rosemount 3051S Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4801, Rev EA
August 2010
Recall Factory Trim—
Sensor Trim
1, 2, 3, 4, 1
Fast Keys
Device Dashboard
Fast Keys

Analog Output Trim

NOTE
Select pressure input values so that lower and upper values are equal to or
outside the 4 and 20 mA points. Do not attempt to obtain reverse output by
reversing the high and low points. This can be done by going to "Rerange" on
page 3-9 of Section 3: Configuration. The transmitter allows approximately
five percent deviation.
4. Follow the commands provided by the Field Communicator to complete
the adjustment of the lower value.
5. Repeat the procedure for the upper value, replacing 2: Lower sensor trim
with 3: Upper sensor trim in Step 3.
AMS
Right click on the device and select "Calibrate," then "Sensor trim" from the
menu
.
1. Select "Lower sensor trim." The lower sensor trim value should be the
sensor trim point that is closest to zero.
2. Click Next after setting the control loop to manual.
3. Click Next after applying appropriate pressure to sensor.
4. Select Next to acknowledge the loop can be returned to automatic
control.
5. Select Finish to acknowledge the method is complete.
6. Right click on the device and select "Calibrate," select "Sensor trim" from
the menu
7. Select "Upper sensor trim" and repeat steps 2-5.
The Recall Factory Trim—Sensor Trim command allows the restoration of the
as-shipped factory settings of the sensor trim. This command can be useful
for recovering from an inadvertent zero trim of an absolute pressure unit or
inaccurate pressure source.
3, 4, 3
Field Communicator
Enter the fast key sequence "Recall Factory Trim—Sensor Trim."
AMS
Right click on the device and select "Calibrate," then "Recall Factory Trim"
from the menu
1. Click Next after setting the control loop to manual.
2. Select "Sensor trim" under "Trim to recall" and click Next.
3. Click Next to acknowledge restoration of trim values is complete.
4. Select Next to acknowledge the loop can be returned to automatic
control.
5. Select Finish to acknowledge the method is complete.
The Analog Output Trim commands allow you to adjust the transmitter's
current output at the 4 and 20 mA points to match the plant standards. This
command adjusts the digital to analog signal conversion (see Figure 4-1 on
page 4-3).