6 Parameter Table

6
Parameter Table
This parameter table shows the most
important parameters. Default settings are
bold type. Refer to the Technical Manual for
a complete list of parameters.
Par.
Name
Initialization Parameters
Selects which parameters are
Access
accessible via the digital operator.
A1-01
Level
0:Operation only
Selection
1:User Parameters
2:Advanced Access Level
Selects the Control Method of the
drive.
Control
0: V/f Control
A1-02
Method
2: Open Loop Vector (OLV)
Selection
5: PM Open Loop Vector (PM)
Note: Not initialized with A1-03!
Resets all parameters to default.
(returns to 0 after initialization)
0:No Initialization
1110: User Initialize (The user
Initialize
A1-03
must first set user parameter
Parameters
values and then store them using
parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
Operation Mode Selection
0:Digital Operator
- d1- values
Frequency
1:Analog input A1 or A2
b1-01
Reference
2:Serial Com - RS-422/485
Selection
3:Option board
4:Pulse Input (Terminal RP)
0:Digital Operator
Run
- RUN and STOP keys
b1-02
Command
1:Terminals - Digital Inputs
Selection
2:Serial Com - RS-422/485
3:Option board connected
EN 28
Description
YASKAWA ELECTRIC TOEP C710606 15E - AC Drive V1000 - Quick Start Guide
Par.
Name
Selects the stopping method when
the run command is removed.
0:Ramp to Stop
Stopping
1:Coast to Stop
b1-03
Method
2:DC Injection Braking to Stop
Selection
3:Coast with Timer (a new run
Reverse
0:Reverse enabled
b1-04
Operation
1:Reverse prohibited
Selection
Phase
Switches the output phase order.
b1-14
Order
0:Standard
Selection
1:Switch phase order
DC Injection Braking
DC
Sets the frequency at which DC
Injection
Injection Braking starts when
b2-01
Braking
Ramp to Stop (b1-03 = 0) is
Start
selected. If b2-01< E1-09, DC
Frequency
Injection Braking starts at E1-09.
Sets the DC Injection Braking
DC
current as a percentage of the drive
Injection
b2-02
rated current.
Braking
In OLV the DC excitation current
Current
is determined by E2-03.
DC Inj.
Braking
Sets the time of DC Injection
Time/DC
Braking at start in units of 0.01
b2-03
Excitation
seconds. Disabled when set to 0.00
Time at
seconds.
Start
DC Inj.
Sets the DC Injection Braking
Braking
b2-04
time at stop. Disabled when set to
Time at
0.00 seconds.
Stop
Acceleration/ Deceleration
Accel
Sets the acceleration time 1 from 0
C1-01
Time 1
to the max. output frequency.
Decel
Sets the deceleration time 1 from
C1-02
Time 1
the max. output frequency to 0.
Description
command is ignored if received
before the timer expires)