6.1.3
Analog Input Block
The follwowing table lists the block errors documented by the Analog Input Block:
Error Code
Description
Out of Service
Target mode is set to
'Out of Service (OOS)'
'Block
Error' is also set
Value of CHANNEL ≠
Block
Configuration
1
Error
Value of L_TYPE is
unspecified.
Unit of XD_SCALE is
not equal to unit of
Transducer Block
parameter
PRIMARY_VALUE_R
ANGE
Some IFC090 measurement problems can be read from the Analog Input Block parameter OUT status. The
following table lists (almost) all of the Analog Input OUT statuses that are mapped to IFC090 (Precondition:
Analog Input Block is configured and target mode is set to Automatic, see 5.3):
OUT status
Good:NonSpecific:NotLi
mited
Bad:NonSpecific.NotLi
mited
Bad:ConfigurationError:
NotLimited
Bad:DeviceFailure:NotL
imited
Bad:DeviceFailure:Con
stant
Bad:SensorFailure:Con
stant
Bad:OutOfService:NotLi
mited
Uncertain:NonSpecific:
NotLimited
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg
Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de
Troubleshooting
Action
If Automatic is the desired target mode, set MODE_BLK target to
'Automatic (Auto)'.
See 'Block Configuration Error' description below.
Configuration
Set the value of CHANNEL to 1.
Set value of L_TYPE to 'Direct', 'Indirect', or 'Indirect Square
Root'.
NOTE:
If set to 'Indirect' or 'Indirect Square Root', don't forget to
configure parameter OUT_SCALE!
Set
PRIMARY_VALUE_RANGE.
NOTE:
Since the unit of PRIMARY_VALUE_RANGE is fixed to m
this always must be m
Description
Action
No IFC090 problem
n/a
detected
Old measurement
Normally, this status will disappear after a short period. If not,
value. The value has
replace signal converter or contact KROHNE service.
not been updated for
a long period of
time.
Analog Input Block
Check parameters CHANNEL, L_TYPE and XD_SCALE.
configuration is
Configure them as described in 5.3.
incorrect.
AD converter error.
Replace signal converter or contact KROHNE service.
Measured value is
Check instrument parameters and correct it if necessary. Error
outside of sensor
messages deleted automatically.
range.
Actual mode is Out
Check the target mode and ensure that it is set to 'Auto' mode.
of Service.
Pipe is empty
Fill the pipe with media.
AD converter
Check instrument parameters and correct it if necessary. Error
overshooted.
messages deleted automatically.
the
unit
of
XD_SCALE
3
/s.