KROHNE IFC 090 Supplementary Installation & Operation Instructions page 11

With foundation fieldbus communications
Table of Contents

Advertisement

Supplementary Documentation
IFC090, IFC090 i with FF
IFC090 FF 01/2005
Parameter
Access
CYCLE_SEL
R/W
CYCLE_TYPE
R
DD_RESOURCE
R
DD_REV
R
DEV_REV
R
DEV_TYPE
R
FAULT_STATE
R
FEATURES
R
FEATURE_SEL
R/W
FREE_TIME
R
FREE_SPACE
R
GRANT_DENY
R/W
HARD_TYPES
R
ITK_VER
R
LIM_NOTIFY
R/W
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg
Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de
IFC090-FF Block Description
Description
Used to select the block execution method for this resource. The following methods
are available:
Scheduled
Completion of block execution
see also: CYCLE_TYPE
Identifies the block execution methods available for this resource.
It is possible to deliver devices which have the DD for its resource within the device.
This parameter assigns the tag where to find the DD in the resource. Since the
IFC090-FF doesn't come with a 'build-in' DD, this value is blank.
Revision associated with the DD of the resource – used by interface devices to locate
the DD file for the resource.
KROHNE revision number associated with this resource – used by interface devices to
locate the DD file for the resource.
KROHNE model number of the IFC090-FF – used by interface devices to locate the
DD file for the resource.
Condition set by loss of communication to an output block.
NOTE:
Since the IFC090-FF doesn't have an output block, this parameter isn't supported.
Used to show supported resource block options. The following features are supported
by the IFC090-FF:
Reports
Soft Write Lock
see also: FEATURE_SEL
Used to select supported features. The following features are selectable:
Reports
enable sending of alert reports
Soft Write Lock
enable soft write locking of parameters
see also: FEATURE_SEL
Available time for configuration of further blocks.
NOTE:
Since the IFC090 blocks are preconfigured, this value is always zero (0).
Available memory for configuration of further blocks.
NOTE:
Since the IFC090 blocks are preconfigured, this value is always zero (0).
Options for controlling access of host computer and local control panels to operating,
tuning and alarm parameters of the block.
NOTE:
This parameter is not supported by IFC090-FF
The type available input signal that is delivered by the Transducer Block and used as
Analog Input Block input parameter. For the IFC090-FF this is 'Scalar Input' (1).
Major revision number of the interoperability test case used in certifying this device as
interoperable.
NOTE:
Due to an error, this value is '0', but has to be '4' (since the IFC090-FF is interoperable
with interoperability test case version 4).
Maximum number of unconfirmed alert notifies messages allowed. This number
always has to be less than MAX_NOTIFY.
see also: MAX_NOTIFY
Page 11 of 44