5.2 % Outside Air (Carbon Dioxide)

To activate % outside air mode, press the
displayed in the middle display area. Press and hold the
displayed.
1) Place the sensor of the 1010 perpendicular to the "Return" air flow. When the
reading stabilizes press the
"C-1" is displayed.
2) Place the sensor of the 1010 perpendicular to the "Supply" air flow. When the
reading stabilizes press the
"C-2" is displayed.
3) Place the sensor of the 1010 perpendicular to the "Outside" air flow. When the
reading stabilizes press the
"C-3" is displayed.
4) Press the
air will be displayed at the top of the display.
5) If you want to perform this measurement again, press the
return to step 1.
6) To exit and return to normal operation, press and hold the
a beep is heard and the 1010 returns to normal operation.
key and capture the return air temperature,
key and capture the supply air temperature,
key and capture the outside air temperature,
key, "C =" will be displayed and the calculated percent outside
key about 2 seconds until "t-0" is
key until "C-0" is
key once and
key until