Note – Make sure you hold the Ethernet hub while removing the screws, as the unit
will fall once all the screws are removed.
10.5
Replacing the Ethernet Hub in the
Second Cabinet
1. Hold the new Ethernet hub in place in the mounting bracket and secure the four
screws (two on the left and two on the right).
2. Moving from right to left, connect the cables back into the appropriate
connections on the Ethernet hub.
3. Connect the power cable into the Ethernet hub.
4. Swing the mounting bracket closed.
5. Secure the two PEM fasteners on the right side of the Ethernet hub mounting
bracket.
6. Close the back door.
10.6
Removing the Mounting Bracket in the
Second Cabinet
These instructions tell how to remove the mounting bracket from the second cabinet
should it become damaged or broken.
mounting bracket.
1. Open the back door.
2. Unscrew the two PEM fasteners on the right side of the Ethernet hub mounting
bracket.
3. Swing open the mounting bracket.
4. Disconnect the power cable from the Ethernet hub.
5. Ensure that all Ethernet cables are labeled and note the ports to which they are
connected.
provides an illustration of the
FIGURE 10-1
Chapter 10 Servicing the Ethernet Hub
10-5