FX2N-8AD Analog input block
9.1

Standard I/O characteristics

Explanation on description
The input mode of the standard I/O characteristics is abbreviated as shown below.
0. Voltage input, -10 to 10V, 20V × 1/32,000
: Input mode set in BFM #0, BFM #1
: Input mode
: Analog input range
: Resolution
Figure 9.1: Standard I/O characteristics
0. Voltage input, -10 to +10 V, 20 V × 1/32,000
Digital value
Approx. +16,320
16,000
Input
voltage
-10
(V)
10
-16,000
Approx. -16,320
Adjustment of I/O Characteristics 9
• In the analog value direct display mode and
the thermocouple input mode,
input range and
Resolution are omitted.
1. Voltage input, -10 to +10 V, 20 V x 1/8,000
Digital value
Approx. +4,080
4,000
Input
voltage
-10
(V)
-4,000
Approx. -4,080
Analog
10
9-2