Mitsubishi Electric FX2N-8AD User Manual page 26

Melsec-f programmable controllers analog input block
Hide thumbs Also See for FX2N-8AD:
Table of Contents

Advertisement

FX2N-8AD Analog input block
Table 7.2: Power supply specifications
Item
Interface driving
power supply
CPU driving power
supply
Table 7.3: Performance specifications
Item
Conversion speed
Insulation method
Number of occupied
I/O points
Applicable PLC
Built-in memory
24 V DC±10%, 80 mA (maximum), supplied via terminal from outside
5 V DC, 50 mA, supplied via extension cable from PLC main unit
• When only voltage input and current input are used
500 µs x Number of used channels
• When thermocouple input is used for 1 or more channels
Channel for voltage/current input: 1 ms x Number of used channels
Channel for thermocouple input: 40 ms x Number of used channels
(Number of used channels indicates number of all channels used for voltage
input, current input or thermocouple input.)
Photocoupler insulates analog input area from PLC.
DC/DC converter insulates power supply from analog I/O.
Channels are not insulated each other.
8 points (including input points and output points)
FX
/FX
/FX
/FX
/FX
0N
1N
2N
2NC
(For connection to FX
Series PLC, FX
2NC
(For connection to FX
Series PLC, FX
3UC
EEPROM
Specifications
Specifications
/FX
Series PLC
3U
3UC
-CNV-IF is required.)
2NC
-1PS-5V or FX
3UC
Specifications 7
-CNV-IF is required.)
2NC
7-2