Ablerex BRIC30S User Manual page 22

Intelligent online ups
Table of Contents

Advertisement

Output electrical characteristics
Technology
Nominal output voltage (selectable)
Power factor at nominal power
Tolerance on the output voltage
Nominal output frequency
Tolerance on the output frequency
Slew rate
Load crest factor
Voltage harmonic distortion (THDv)
Overload capability by the inverter
Voltage unbalance
Dynamic output voltage regulation
Phase displacement
By-pass electrical characteristics
Technology
By-pass nominal voltage
By-pass rated voltage range
By-pass rated frequency
Tolerance on by-pass frequency
Battery
Battery type
Workable numbers in a string
Bridge with IGBT
3x380/400/415V+N
0.9
Static: ±1%
Dynamic: ±5% (0~100% or 100~0% stepping load)
50/60Hz (auto sensing)
±0.1% when free running
< 1Hz/s
3:1 acceptable
< 3% with linear load
< 5% with distorting load
110% load for 60 minutes
125% load for 10 minutes
150% load for 1 minute
2% maximum with 100% unbalanced load
±5% with 100% stepping load
return to ±1% within 50ms
120°±1° with 0~100% balanced load
120°±3° with 100% unbalanced load
Thyristors
380/400/415V
Inverter voltage ±10% (Lo-sensitive);±5% (Hi-sensitive)
(Selectable)
50/60Hz (auto sensing)
±3Hz (Lo-sensitive);±1Hz (Hi-sensitive) (Selectable)
Lead-acid battery
32/34/36/38/40pcs depending upon configuration
42
Common battery feature
Floating charge voltage
Cut-off voltage
Max charging current
Efficiency
Efficiency in dual conversion mode
Efficiency in "ECO Mode"
Efficiency in backup mode
19232125200200
Yes
2.30V/cell
1.60V/cell
10Adc
> 93%
> 97%
> 93%
43

Advertisement