Download Print this page

Technical Gas Data Table - Lotus CP-94G Operation & Maintenance Instructions Manual

Pasta cooker for professional use

Advertisement

MODEL
DIMENSIONS cm
TOTAL NOMINAL POWER(BTU/h)
GAS CONNECTION
WATER FILLING
WATER DRAINAGE
1.48.1 i, p
The appliance must be installed in accordance with the ANS Z83.11a CSA 1.8a-(2001) Food Service
Equipment,
The operations for installing, conversions for use with other types of gas and starting up must be done only by
qualified personnel whose qualifications comply with the norms in force.
Gas installations, the electrical connections and the rooms in which the appliances are installed must comply with
the norms in force in the Country in which the installation is carried out; above all, the appliance must be installed
in a well ventilated room, preferably under an extractor hood, so as to ensure the complete extraction of gas
emissions which are formed during combustion. The air necessary for combustion is 2m3 /h per kW of power
installed.
Attention! In accordance with international rules, when connecting the appliance, an automatic device enabling the
disconnection of all contacts from the mains, must be installed above it; this device must have a contacts opening of at
least 3 mm.
CHECKING FOR CORRECT VENTILATION AND COMBUSTION AIR
1.48.1 p
Ensure that the air outlets in the place of work are sufficient to guarantee the necessary air exchange, as stated
in paragraph 4.3 of the UNI-CIG. norm 8723.
The appliance may be installed as a single element or in series with other appliances of our production. It is necessary to
observe a minimum distance of 10 cm from the appliance to prevent contact with walls of inflammable material;
adequate measures must also be taken to ensure thermal insulation of inflammable parts, such as the installation of a
protection against radiation; particular attention must be paid in installing the appliances adequately and safely. The feet
are adjustable in height so that differences in level can be avoided.
The machine must be place in conditions of optimal ventilation: the area for the combustion of the item comes captured
from the bottom of the same one.
The minimal necessary area for the combustion is given from the minimal height of the feet mounted on the machine,
therefore the machine cannot be installed without the adjustable feet.
The gas connection must be done with steel pipes, or otherwise with flexible steel pipes in compliance with the national
norms, if any exist. Each appliance must be provided with a cut-off cock for rapid interruption of the gas supply. Once
the appliance has been installed, it is necessary to check for gas leaks for the pipe fittings; do not use a flame for this
purpose but a non-corrosive substance such as soapy water or foamy substances as contained in leak-finder sprays. All
our appliances undergo careful testing: the type of gas, the operating pressure and the category are indicated on the data
plate.
NB: The year of the appliance manufacture is shown in item "N" on the data plate. The first two numbers (e.g. 08...)
represent the year of manufacture.
The appliances must be checked in such a way as to verify that the heat output is correct:
The heat output (thermal power) is indicated on the data plate of the appliance.
Firstly, check that the appliance can be used with the type of gas supplied; then check that the indication on the
plate corresponds to the gas to be used. For converting to another type of gas, check that the type of gas complies
with what is stated in this instruction manual.
The pressure is read with a gauge inserted in the relative pressure outlet..
Remove the hermetically closed screw and insert the gauge pipe.
After reading, put back the screw tightening it hermetically and check for pressure leaks.
Connection for liquid gas (Propane HD-5)
The connection pressure for liquid gas is 2.74 kPa with Propane HD-5.
USA

TECHNICAL GAS DATA TABLE

INSTALLATION
PIPE FOR GAS CONNECTION
CHECKING HEAT OUTPUT
9
CP-94G
CP-98G
40x90x90h
80x90x90h
47,600
95,200
R 1/2GM
R 1/2GM
R 1/2GM
R 1/2GM
R 1GF
R 1GF

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Cp-98g