KVCG202/EN M/H11
The relay will only respond to the commands via serial port if link SD2=1.
Setting SD2=0 inhibits all remote commands over the serial port.
The following cell locations are allocated to store three levels of loadshedding/boosting in
the CONTROL column of the menu system.
LEVELS
Level 1
Level 2
Level 3
The following truth table then applies:
COURIER COMMAND
Level 0
Level 1
Level 2
Level 3
7.6.2

Local control of loadshedding/boosting

Local loadshedding/boosting control of the relay are via using the opto inputs assigned in
input mask. The three levels can be selected by energising one of the three opto input
channels as required by the user. If more than one opto inputs are energised at any one
time then the relay acts on the setting nearest to 0.
For example, if
Level1 = 3 % and Level 2 = +9 %, then level 1 is selected OR
Level1 = 3 % and Level 2 = –3 % then level 2 is selected. The –ve setting has priority
over the +ve setting if both values are equally nearest to 0.
The following cell locations are assigned in the input masks.
LEVELS
Level 1
Level 2
Level 3
Cell Location
030E
030F
0310
SELECT
None
Select level 1 setting
Select level 2 setting
Select level 3 setting
Cell Location
0707
0708
0709
Technical Manual
KVGC202