Directional - GE KVGC 202 Technical Manual

Voltage regulating control
Table of Contents

Advertisement

KVCG202/EN M/H11
8.9.3

Directional

Operating boundary
PU – DO differential
8.9.4
Measurements
Measured voltage
Load current
Circulating current
Power factor
Frequency
(45 – 65Hz)
8.10
Influencing quantities
8.10.1
Ambient temperature
Operative range
Current settings
Voltage settings
Operation times
Angle measurement
8.10.2
Frequency
With frequency tracking
Operative range
Current setting
Voltage settings
Operating times
Angle measurement
Without frequency tracking
Reference range
Operating times
8.10.3
Angle measurement <2°
Auxiliary supply
Current settings
Voltage settings
Operation times
Angle measurement
0 – 180° accuracy ±3°
less than 3° (typically <1°)
±2% Vn (typical)
±0.3% Vn over the range 70 – 160V (typical)
I
±2%
n (typical)
I
±5%
n (typical)
I
±10%
n at <100mA
±5%
±1% (typical)
–25 to +55°C
±1%
±0.03% per °C
±1%
<2°
46 to 65Hz
±1%
±1%
±1%
<1°
47Hz to 51Hz or 57Hz to 61Hz
±2%
Nominal
Operative range
24/125V
19 to 150V dc
50 to 133V ac
48/250V
33 to 300V dc
87 to 265V ac
±0.5%
±0.5%
±0.5%
±0.5°
Technical Manual
KVGC202

Advertisement

Table of Contents
loading

Table of Contents