Logic Links (Log) - GE KVGC 202 Technical Manual

Voltage regulating control
Table of Contents

Advertisement

Technical Manual
KVGC202
The following options are available via links SD0 to SD7:
SD0
SD1
SD2
SD3
SD4
SD5
SD6
SD7
SD8
SD9
When the selection has been completed continue to press the [F] key until the
confirmation display appears and confirm the selection.
Now step down the menu to cell [0004 Description] and enter a suitable name for the
configuration; a maximum of sixteen characters are available.
Step down one cell [0005 Plant Ref.], where a suitable reference can be entered for the
plant that the relay is to protect. If the configuration is for a relay that is to be applied to
one particular circuit, then the reference by which the circuit is known can be entered at
this time; a maximum of sixteen characters are available.
Now move down the SYSTEM DATA column to cell [0009 Freq] and set the frequency to
50Hz or 60Hz as appropriate. This is an important setting because it will be the default
frequency used by the analogue/digital converter when appropriate signals are not
available for frequency tracking.
If the address of the relay on the serial communication bus is known then it can be
entered at this time. This cell is password protected on the series 2 relays.
This concludes the settings that can be entered in this menu column at this time.
4.2.2

Logic links (LOG)

The Logic Links under the LOGIC menu column heading customise the auxiliary
functions of the relay.
pressing the [+] key. Step through the function links with the [F] key and set the links for
the options required.
LOG0
LOG1
LOG2
LOG3
LOG4
LOG5
LOG6
LOG7
LOG8
LOG9
When the selection has been completed continue to press the [F] key until the
confirmation display appears and confirm the selection.
Not used
Rem Cntrl
1 = enable remote control
Rem LSB
1 = enable load shedding/boost
Rem Grp2
1 = enable remote change to group2 settings
En Grp2
1 = enable group 2 settings
0 = hide group 2 settings
1 = Grp2
1 = select group 2 settings
Irev = Grp2
1 = reverse current selects group 2
Log Evts
1 = enable storing of logic changes in event recorder
Not used
Extrn V
1 = TPI uses external voltage VT
To modify these settings put the relay into setting mode by
Not used
TpFail
1 = Block if outside dead time for max time
1 = Block for excessive circulating current
I
> Blk
C
1 = Block for excessive load current
I
> Blk
L
total opsBlk
1 = Block for excessive number of operations
Freq opsBlk
1 = Block for frequent operations
1 = Block for reverse current
I
Blk
rev
Runaway Blk
1 = Block for tap change runaway
1 = Reverse current to select group 2
I
Grp 2
rev –
Il<blk
1 = Block for insufficient current
KVCG202/EN M/H11