Menu Columns; System Data - GE KVGC 202 Technical Manual

Voltage regulating control
Table of Contents

Advertisement

Technical Manual
KVGC202
3.3.4

Menu columns

Col No
Heading
00

SYSTEM DATA

01
STATUS
02
MEASURE
03
CONTROL 1
04
LOGIC 1
05
CONTROL 2
06
LOGIC 2
07
INPUT MASKS
08
RELAY MASKS
The menu cells that are read only are marked
Cells that can be set are marked
Cells that can be reset are marked
Cells that are password protected are marked
3.3.5
System data
Cell
Text
0000
SYSTEM DATA
0002
Password
0003
SD Links
0
1
Rem Cntrl
2
Rem LSB
3
Rem Grp2
4
En Grp2
5
1=Grp2
6
I
rev=Grp 2
7
Log Evts
8
9
Extrn V
0004
Description
0005
Plant Ref.
0006
Model
0008
Serial No.
0009
Freq
000A
Comms Level
000B
Rly Address
000C
Plnt Status
Description
Settings and data for the system – relay and serial
communications.
Settings for tap control modes
Display of directly measured and calculated quantities
Settings for group 1 miscellaneous control functions
Settings for group 1 miscellaneous logic functions
Settings for group 2 miscellaneous control functions
Settings for group 2 miscellaneous logic functions
User assigned allocation of logic input
User assigned allocation of output relays
Status
Description
READ
Column heading
PWP
Password that must be entered before certain settings
may be changed
PWP
Function links that enable the user to enable (activate)
the options required
1= enable remote control
1= enable remote load shedding/boosting
1= enable remote change to group 2 setting
1= enable group two settings; 0 = hidden
1= select group 2 settings
1= enable reverse current select group 2 settings
1= enable logic changes in event records
1= TPI uses external V ref; 0=TPI uses system voltage
PWP
Product description – user programmable text
PWP
Plant reference – user programmable text
READ
Model number that defines the product
READ
Serial number – unique number identifying the
particular product
SET
Default sampling frequency - must be set to power
system frequency
READ
Indicates the Courier communication level supported
by the product
SET
Communication address (1 to 255)
READ
Binary word, used to transport plant status information
over communication network
KVCG202/EN M/H11
[READ]
[SET]
[RESET]
[PWP]

Advertisement

Table of Contents
loading

Table of Contents