Auxiliary Supply Tests; Auxiliary Supply; Energisation From Auxiliary Voltage Supply; Field Voltage - GE KVGC 202 Technical Manual

Voltage regulating control
Table of Contents

Advertisement

KVCG202/EN M/H11
9.3

Auxiliary supply tests

9.3.1

Auxiliary supply

The relay can be operated from either an ac or a dc auxiliary supply but the incoming
voltage must be within the operating range specified in Table 1.
Relay rating (V)
Table 1
CAUTION: The relay can withstand some ac ripple on a dc auxiliary supply.
9.3.1.1

Energisation from auxiliary voltage supply

For secondary injection testing using the test block type MMLG, insert test plug type
MMLB01 with CT shorting links fitted. t may be necessary to link across the front of the
test plug to restore the auxiliary supply to the relay.
Isolate the relay contacts and insert the module. With the auxiliary supply disconnected
from the relay use a continuity tester to monitor the state of the watchdog contacts as
listed in Table 2.
Connect the auxiliary supply to the relay. The relay should power up with the lcd showing
the default display and the centre green led being illuminated; this indicates the relay is
healthy. The relay has a non-volatile memory which remembers the state (ON or OFF) of
the led control indicator when the relay was last powered, and therefore the indicator may
be illuminated. With a continuity checker, monitor the state of watchdog contacts as
listed in Table 2.
Terminals
3 and 5
4 and 6
Table 2
9.3.1.2

Field voltage

The relay generates a field voltage that should be used to energise the opto-isolated
inputs. With the relay energised, measure the field voltage across terminals 7 and 8.
Terminal 7 should be positive with respect to terminal 8 and should be within the range
specified in Table 3 when no load is connected.
Nominal dc rating (V)
48
Table 3
9.4

Settings

All relays will leave the factory with the recommended settings for the KVGC202 relay
under normal operating conditions, set for operation at a system frequency of 50Hz (refer
to Chapter 5 Section 5.3). If operation at 60Hz is required then this must be set as
follows:
From 'SYSTEMS DATA' menu, press the 'F' key until '0009 Freq 50Hz' appears on the
lcd. Press the '+' key until the display shows '0009 Freq 60Hz'. Then press the 'F' key
once more followed by the '+' key to confirm the change.
DC operating
AC operating
range (V)
24/125
19 – 150
48/250
33 – 300
However, in all cases the peak value of the auxiliary supply must
not exceed the maximum crest voltage. Do not energise the relay
using the battery charger with the battery disconnected.
With relay de-energised
contact closed
contact open
Range (V)
45 – 60
Technical Manual
Maximum crest
range (VAC)
voltage (V)
50 – 133
190
87 – 265
380
With relay energised
contact open
contact closed
KVGC202