KVGC202
5.

RELAY SETTINGS

5.1
Relay settings
All the settings can be entered into the relay via the front keypad or using a PC with a K-
Bus connection. The selection can be made in the menu columns for settings, but
password might be required before some settings can be entered. Two setting groups
are available to allow the user to set Group 1 to normal operating conditions while Group
2 can be set to cover abnormal operating conditions.
The quantities that require setting are listed below with the adjustment range and step
sizes:
Setting
Setting voltage
Dead band
Circulating current
Load current
Load current
Circulating current
compensation
Resistive line drop
compensation
Reactive line drop
compensation
Reverse reactance
control
Initial delay (tINIT):
Intertap delay
Tap pulse duration
Load (3 Steps)
shedding/boosting
Under voltage detection
Over voltage detection
Under voltage blocking
Total taps available
Maximum tap position
Minimum tap position
Total no. of tap changes
Tap changer operations
Time period
Excessive circulating
current time delay
Alarm initiation time delay
Power factor angle setting
tV<V>
Symbols
KVGC adjustment range
Vs
90 – 139V
dVs
±0.5% to ±20% of Vs
I
c
0.02 – 0.5A (
0.1 – 2.5A (
I
L>
0.5 – 2A (
2.5 – 10A (
I
I
L<
0 – 1A (
I
0 – 5A (
Vc
0 – 50V
Vr
0 – 50V
Vxl
0 – 50V
Internal reversal of V
Definite
0 – 20 secs
20 – 300 secs
Inverse
See Chapter 6.3.3
tINTER
0 – 120 secs
tPULSE
0.5 – 5 secs
0 – ±10% of Vs
V<
80 – 130V
V>
105 – 160V
V<<
60 – 130V
TapsAvail
1 – 30 Ext volt/1– 40 VT
TP>
1 – 30 Ext volt/1– 40 VT
TP<
1 – 30 Ext volt/1– 40 VT
TotalOps>
1 – 10000
Ops/tP>
1 – 100
tP
1 – 24 hrs
0 – 180 secs
tI
C
tFAIL>
0 – 15 mins
PF Angle
0 – 90 degrees
tV<V>
0 – 300 secs
KVCG202/EN M/H11
I
n = 1A)
I
n = 5A)
I
n = 1A)
I
n = 5A)
n = 1A)
n = 5A)
vector
XL
In steps of
0.1V
0.1%
0.01A
0.05A
0.05A
0.10A
1.0V
1.0V
1.0V
1 sec
10 secs
0.1 secs
0.5 secs
1%
1.0V
1.0V
1.0V
1
1
1
1
1
1 hr
10 secs
30 secs
1 degree
5 secs