Error Codes - Samsung MIM-E03 series Installation Manual

Control kit
Hide thumbs Also See for MIM-E03 series:
Table of Contents

Advertisement

Error codes

If the unit has some problems and does not work normally, error code is shown on the OUTDOOR UNIT main PBA or LCD of
the wired remote controller .
Display
101
CONTROL KIT / OUTDOOR UNIT wire connection error
162
EEPROM Error
201
CONTROL KIT/OUTDOOR UNIT communication error (Matching error)
202
CONTROL KIT/OUTDOOR UNIT communication error (3 min)
203
Communication error between INVERTER and MAIN MICOM (6 min)
221
OUTDOOR UNIT temperature sensor error
231
condenser temperature sensor error
251
Discharge temperature sensor error
320
OLP sensor error
403
Detection of OUTDOOR UNIT compressor freezing (During cooling operation)
404
Protection of OUTDOOR UNIT when it is overload (during Safety Start, Normal operation state)
416
Discharge of a compressor is overheated
419
OUTDOOR UNIT EEV operation error
425
Power source line missing error (only for 3-phase model)
440
Heating operation blocked (outdoor temperature over 35°C)
441
Cooling operation blocked (outdoor temperature under 9°C)
458
OUTDOOR UNIT fan1 error
461
[Inverter] Compressor startup error
462
[Inverter] Total current error/PFC over current error
463
OLP is overheated
464
[Inverter] IPM over current error
465
Compressor V limit error
466
DC LINK over/low voltage error
467
[Inverter] Compressor rotation error
468
[Inverter] Current sensor error
469
[Inverter] DC LINK voltage sensor error
470
EEPROM read/write error
471
[Inverter] OTP error
474
IPM(IGBT Module) or PFCM temperature sensor Error
475
OUTDOOR UNIT fan2 error
484
PFC Overload Error
485
Input current sensor error
500
IPM is overheated
554
Gas leak error
601
Communication error between the CONTROL KIT and wired remote controller
602
Wired remote controller Master/Slave setting error
604
Communication tracking error between the CONTROL KIT and wired remote controller
38
EHS Control unit_MIM-E03@_IM_E_34413-2.indd 38
Explanation
Error Source
CONTROL KIT /
OUTDOOR UNIT
CONTROL KIT
CONTROL KIT /
OUTDOOR UNIT
CONTROL KIT /
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
OUTDOOR UNIT
WIRED REMOTE
CONTROLLER
WIRED REMOTE
CONTROLLER
CONTROL KIT /
WIRED REMOTE
CONTROLLER
2012-04-05 오후 1:20:13

Advertisement

Table of Contents