Samsung MIM-E03 series Installation Manual page 13

Control kit
Hide thumbs Also See for MIM-E03 series:
Table of Contents

Advertisement

Wiring works
Power and communication with outdoor unit
ELCB
L N
Power Wire
• Be careful when connecting L, N .
CAUTION
Connecting the power wire
1 . Connect 'Live' and 'Neutral' power line with 'L, N' of a ELCB .
2 . Connect 'L,N' of a ELCB with 'A1 and A2' in TB-A .
3 . Connect 'Protective Earth' line with 'Earth screw' In case .
Recommended wire specification
Load
Do NOT use Heater (Water Pump,
Valve, Wired RMC)
Use Booster Heater (Max. 3kW)
f The power cable is not supplied with air conditioner
f
f This equipment with "IEC 61000-3-12" .
f
f Supply cords of parts of appliances for control kit use shall not be lighter than polychloroprene sheathed flexible cord
f
(Code designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
Connecting the communication wire
f Connect 'outdoor unit's F1&F2' with 'control kit's F1&F2 in TB-C' by 2 core cable .
f
Control Kit
12
EHS Control unit_MIM-E03@_IM_E_34413-2.indd 12
Power Cable
Power Supply
mm
2
1 . 5 / 3
2 . 5 / 3
1Ø, 220-240V, 50Hz
4 . 0 / 3
6 . 0 / 3
Outdoor Unit
(at Control Plate)
Communication Wire
Main PCB
Max. Length
, wires
m
L < 10m
10m < L
L < 10m
10m < L
2012-04-05 오후 1:19:59