Samsung MIM-E03 series Installation Manual page 25

Control kit
Hide thumbs Also See for MIM-E03 series:
Table of Contents

Advertisement

Wiring works
Wiring a 2way valve for zone#1 (Floor heating)
• When outlet water temperature reach to lower than 16°C in cooling mode, Zone#1 2way valve is closed .
NOTE
1 . Using the appropriate cable, connect a valve control cable to the TB-B
f Initial status of a valve for zone#1 has to be opened.(flow)
f
❈ In case of normal closed type
TB for zone#1
B11
❈ In case of normal opened type
TB for zone#1
B11
• Wiring is different for a N/C(normal closed) valve and a N/O(normal open) valve .
WARNING
2 . Fix the cables with cable ties to the cable tie mountings to ensure strain relief .
24
EHS Control unit_MIM-E03@_IM_E_34413-2.indd 24
TB-B(Control kit
B12
B13
B14
terminal block)
2way valve
*N/C(Normal closed)
(N/C type)
TB-B(Control kit
B12
B13
B14
terminal block)
2way valve
*N/O(Normal open)
(N/O type)
f When it is opened
f
f When it is closed
Mixing
Mixing
Zone#1
Tank
Tank
2way
valve
f When it is opened
f
f When it is closed
Mixing
Mixing
Zone#1
Tank
Tank
2way
valve
f
Zone#1
2way
valve
f
Zone#1
2way
valve
2012-04-05 오후 1:20:05