DEVICENET PROTOCOL
3-42
8.
Click the double arrow (>>)to move the MM200 from the Available Devices list to the
Scanlist. Select Major Revision as the part of the electronic key for MM200.
9.
Double-click MM200 in the Scanlist. The Edit I/O Parameters dialog (shown below)
appears for the MM200.
10. The I/O parameters define the configuration for the device in terms of how much and
what data the device exchanges with the 1747-SDN module. By default, the MM200
will send 38 bytes of input data and will receive 1 byte of ouput data from the poll
connection.
11. Verify that the MM200 parameters are set as shown below:
12. Click OK to close the MM200 Edit I/O Parameters dialog.
13. Click OK again.
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 3: FIELDBUS INTERFACE