Profibus Dpv1-Diagnostics - GE Multilin MM200 Communications Manual

Motor management system
Hide thumbs Also See for MM200:
Table of Contents

Advertisement

PROFIBUS DPV1

Profibus DPV1-Diagnostics

3-18
2.
Add code 3000H to access the Actual Values area or 4000H to access the Setpoint
area
3.
Split the composed 32 bits word found above (DWORD) into 2x16 bits words format
These words will be used to define the DP-V1 Slot (most significant word) and Index
(least significant word).
Read Actual Value examples (Modbus function 04H):
Data to be Read
Actual Value
Address (hex)
Product Information -
0002
firmware version
Product Information -
0007
serial number
Product Information -
0007 to 000D
serial number and
order code
Last Trio Data -
00B9
cause of last trip
Contact Status -
01CH
Contact Input 7-1
User Map Values
020B
1 to 32
Read Set Point examples (Modbus function 03H):
Data to be Read
Setpoint Address
(hex)
Communication
00AB
Settings- slave
address
Motor Data Setup-
011C
motor name
Auto/Manual Control-
0623 - 0633
all data
Error codes:
Profibus DPV1 Error Code
Invalid slot
Invalid index
MM200 DPV1 diagnosis data is structured as shown below:
The extended diagnosis consists of Process Alarms and Diagnostic Alarms.
Trip, Alarm, and Control status are categorized as Process Alarms, as these provide
information pertaining to the Motor health that MM200 is controlling and monitoring.
Messages are categorized as Diagnostic Alarms as these provide detailed MM200
diagnostic information.
The detailed message layout explaining what information each bit provides is as follows:
DPV1 Composed
Address (hex)
0002 + 3000 = 3002
0007 + 3000 = 3007
0007 + 3000 = 3007
00B9 + 3000 = 30B9
011C + 3000 = 311C
020B + 3000 = 320B
DPV1 Composed
Address (hex)
00AB + 4000 = 40AB
011C + 4000 = 411C
0623 + 4000 = 4623
Cause
Wrong code was added to the slot. Ensure 3000H or 4000 was added
to the memory map address issued to the device.
An invalid memory area was defined. It can be caused by a base
invalid memory address or a request to read a reserved memory area.
Ensure the base address is correct and that a valid length was
specified.
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 3: FIELDBUS INTERFACE
DPV1 Parameters
Length
(hex)
(bytes)
Slot
Index
30
02
2
30
07
12
30
07
44
30
B9
2
31
1C
2
32
0B
64
DPV1 Parameters
Length
(hex)
(bytes)
Slot
Index
40
AB
2
41
1C
20
46
23
17