CHAPTER 3: FIELDBUS INTERFACE

Profibus Output Data

Profibus DPV0-Diagnostics

MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
Category
The capability to reset, stop, and start the motor has been made available via the Profibus
Output data. Because polled output data is continuously written to the slave device, the
MM200 looks for a change in the value to execute any command.
Byte
Bit Number
0
0 to 7
8
9
10
1
11
12
13
14
15
Table 3-4: Data Value, polled output data
VALUE
DESCRIPTION
1
Reset
2
Lockout Reset
4
Stop
8
Start A
16
Start B
66
Clear Last Trip Data Prompt
68
Clear Counters
71
Clear Maintenance Timer
73
Reset Motor Information
74
Auto Mode
75
Manual Mode
The MM200 supports both slave mandatory (6 bytes system-wide standardized) and slave
specific extended diagnostic data. If the diagnostics are considered high priority, the PLC/
host program will be informed of the fault (alarm, trip, command, or message) and can call
a special error routine. When no extended diagnostic information is available and the
master initiates a diagnostics read, only the six standard slave mandatory bytes are read,
formatted as follows:
Address
Description
76
Pre Trip Motor Load
78
Pre Trip Current Unbalance
80
Pre Trip Ig
84
Reserved
Bit Mask
01
02
04
08
10
PROFIBUS DP
Format
F1
F1
F10
Description
Reserved Byte
Reset
Lockout Reset
Stop
Start A
Start B
Reserved Bit
Reserved Bit
Reserved Bit
3-7