Fieldbus Interface; Profibus Dp - GE Multilin MM200 Communications Manual

Motor management system
Hide thumbs Also See for MM200:
Table of Contents

Advertisement

GE
Grid Solutions
MM200 Motor Management System
Chapter 3: Fieldbus interface

Profibus DP

MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE

Fieldbus interface

The fieldbus interface is configurable as either Profibus DPV0/V1 or DeviceNet. Both
Fieldbus interfaces support control and status – refer to the specific data map below for
details.
Note that external power, 5 to 24 VDC, is required for this interface to operate. (Ensure that
switches 7 and 8 of the DIPswitch on the communication card, are ON.) A GSD file is
provided on the GE Multilin website http://www.gedigitalenergy/com .
To enable the Profibus physical interface, ensure that switches 3 and 4 of the DIP switch on
the communications card (on the CPU module) are ON, and that switches 1 and 2 are OFF.
The external connections through the Fieldbus interface are as follows:
Table 3-1: Fieldbus interface external connections (Profibus)
Pin
V–
L
C
H
V+
Table 3-2: DB9 signal pin applicability to MM200
DB9 pin (external device)
1
2
3
4
5
6
Connection (external device)
Pin 5
Pin 8, line A (negative TX/RX)
Common drain
Pin 3, line B (positive TX/RX)
Pin 6
MM200 pin
Signal
C
(shield)
No connection
M24
H
RxD/TxD-P
No connection
CNTR-P
V-
DGND
V+
VP
Description
Shield or potential equalization
Ground of 24V power supply
Receive/Transmit data; line B (red)
Repeater control
Data ground (reference voltage to VP)
Power supply*
1
3-1

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for GE Multilin MM200

Table of Contents