CHAPTER 3: FIELDBUS INTERFACE
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
The following diagram shows an example of the extended diagnostic data sent to the
Profibus master by the MM200. The extended diagnostic data is only provided when one of
the states listed in the above extended diagnostic table has become true. In this example,
the extended diagnostic data has been sent because the "External Start A Alarm" is active.
Such a case would occur when the motor status is running, but no Start A control was
issued by the MM200.
Figure 3-7: Profibus - extended diagnostic data
The diagram below shows an example of the standard diagnostic data, which is sent once
to the Profibus master after all Extended Diagnostic conditions become false (when
previously true), or if the master specifically issues a diagnostic data request.
Byte
Bit
GSE Bit #
44
0
296
44
1
297
44
2
298
44
3
299
44
4
300
44
5
301
44
6
302
44
7
303
45
0
304
45
1
305
45
2
306
45
3
307
45
4
308
45
5
309
45
6
310
45
7
311
PROFIBUS DP
"Forward Limit"
"Reverse Limit"
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
"Any Stop"
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Ext.
Diag
Byte
38
38
38
38
38
38
38
38
39
39
39
39
39
39
39
39
3-15

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for GE Multilin MM200

Table of Contents