CHAPTER 3: FIELDBUS INTERFACE
NOTE:
NOTE
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
1.
Before switching ON the network power make sure that the MACID of MM200 is set to
something other than 63.
2.
Switch on the power supply to the chassis that will power up the device.
3.
Switch on the power to the 1770 KFD module and the MM200 relay.
External power must be present on the DeviceNet port of the MM200 relay at power-up, in
order to correctly initialize and operate.
Configuring the driver using RSLinx
After the network is set up the first task is to configure the DeviceNet driver on the PC.
Follow these steps to configure the DeviceNet driver:
1.
Start RSLinx software. The RSLinx main dialog opens.
2.
Select Configure Drivers from the Communication menu.
The following dialog appears:
DEVICENET PROTOCOL
3-31