Application Example 2(Connecting to the Mitsubishi Standard
PLC FX Series.)
System Configuration
This section uses the following example to describe how to access a G9SP-series
Controller by performing serial communications through a RS-232C Serial
Communications Board (CP1W-CIF01) from a Siemens Standard PLC FX series.
Mitsubishi Standard PLC(See Note.)
Note:
CPU Unit (Standard PLC)
RS-232C Communication Adapter
Support Software (for setup and creating ladder
programs)
G9SP-series Controller Settings
Settings are not required. Make the communications settings in the Mitsubishi
Electric Standard PLC to match the serial communications specifications of the
G9SP-series Controller.
Mitsubishi Electric PLC FX series Settings
Set RS-232C communication adapter CH1 as given below in the PLC parameter
using the GX Developer.
PLC parameter settings
Set RS-232C communication adapter CH2 as given below in the PLC parameter
by selecting[Project data list]-[Parameter]-[PLC parameter]-[PLC System(2)].
Protocol
Data length
Parity
Stop bit
Transmission Speed
Header
H/W Type
Transmission control
procedure
Time out judge time
2-10
Communi
MELSEC-FX
cation
series
Adapter
CP1W-CIF01
Option Board
This example uses the following Mitsubishi Electric Standard PLC.
Product
Parameter
Communication protocol
Transmission setting
Baud rate
Set the header.
Normally choose RS-232 or
RS-485.
Choose format 1/format 4.
Set the time-out period.
Non procedure
G9SP-series
FX3UC-32MT-LT
FX3U-232AP
GX Developer Version 8.90U
Description
Model/Version
Set value for this
example
Non-procedural
8bit
Even
1bit
9600
Yes
Regular/RS232C
Form1(without
CR,LF)
30(300msec)