G9SP-series Controller Settings
Make the settings for TCP/IP in the system settings of the G9SP Configurator.These
settings are set in the G9SP-series Controller and Ethernet Option Board
when the configuration data is downloaded.
Parameter
IP address
Subnet mask
Default gateway
FINS node address
FINS/UDP port
IP address table
3-12
IP address of Ethernet Option Board.
Default value: 192.168.250.1
Subnet mask of Ethernet Option Board.
Default value: 255.255.255.0
Set the IP address of the default gate-
way. Default value: 0.0.0.0 (IP routing not supported)
Set the FINS node address of the Ethernet Option Board. If
automatic setting is specified, a value that matches the rightmost
byte of the IP address is stored.
Default value: Automatic (matching the
rightmost byte of the IP address)
Setting range: 1 to 254
Specify the UDP port number that is specified in the FINS
communications service. The UDP port number is a number
used by UDP to identify the application layer (here, the FINS
communications service).
Default value: 0 (9600)
Setting range: 0 to 65535. When set to
0, the FINS/UDP port number is 9600.
Set the table that defines correspondence between the FINS
node address and IP address at the Standard PLC.Set the IP
address table when IP routing is used.
Description
Set value for this
example
192.168.250.2
No change is
required.
No change is
required.
No change is
required.
No change is
required.
No change is
required.