Single Point Status (Sps) - ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

3.4.8.17.
44
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Send All Updates
True
False
Default: False
Send As Double
True
Point
False
Default: False
Send As Inverse
True
Value
False
Default: False
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time

Single point status (SPS)

Table 3.4.8.17-1 Configurable SPS properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
SPS
Class
Addresses
Indication Index
0...65535
Default: 0
Common
Class
Class 0...3
Default: Class 0
Description
Defines if all changes in value are sent to
the master.
Defines if a value is sent as double point.
Defines if the value of a message is
inverse.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC
61850
Indication index.
Class of ASDU. Data sent from the slave
to the master can be assigned to four
classes. Data in class 1 is sent with higher
priority than data in class 3.
1MRS756567

Advertisement

Table of Contents
loading

Table of Contents