1MRS756913
3.4.5.16.
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Update Rate
0...60000
Default: 0
Data Specific
Received as Inverse
True
Control Value
False
Default: False
Send as Double
True
Point
False
Default: False
Send as Inverse
True
Value
False
Default: False

Single point status (SPS)

Information in the following table applies also to the Internal SPS data object.
Table 3.4.5.16-1 Configurable SPS properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
SPS
Class
Addresses
Address
0...65535
Default: 0
Common
Update Rate
0...60000
Default: 0
Data Specific
Description
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Specifies if a control value is received as
an inverse value.
Specifies if a value of an indication signal
is sent as a double point value.
Specifies if a value of an indication signal
is sent as an inverse value.
Description
Common data class according to IEC
61850.
Address.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
37