ABB i-bus® KNX PARAMETERS
7.4.41

Actual temperature receipt

This parameter is used to define how the controller receives the actual temperature.
If a temperature sensor is not connected to any of the inputs, the controller changes to safety mode.
If several inputs are set as temperature sensors, a mean value is formed from the measured values and
is used as the actual temperature value.
Option
Via physical device input
Via group object
Via phys. device input or group
object
Prerequisites for visibility
• Parameter window
function
• The parameter is in the parameter window
7.4.42

Dew point status receipt

This parameter is used to define how the controller receives the dew point status.
If no input is set as the dew point sensor, the controller interprets the function as being deactivated.
If several inputs are set as dew point sensors, they are logically OR-linked. The controller reacts as
soon as one of the inputs sends the status "Dew point reached".
Option
Deactivated
Via physical device input
Via group object
Prerequisites for visibility
• Parameter window
– Parameter
– Parameter
• The parameter is in the parameter window
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page
Note
The controller checks which device input is parameterized as a temperature sensor. The measured
actual temperature is included in control.
The actual temperature is received via max. two group objects. The received values are weighted.
The following dependent parameters are shown:
Number of group objects Actual temperature
The actual temperature can be received via a device input and/or via group objects. The values
measured on the inputs and received via the bus (ABB i-bus® KNX) are weighted.
The following dependent parameters are shown:
Number of group objects Actual temperature
Weighting of internal measurement
Weighting of external measurement 1
Channel X
Controller channel
\ Option
Note
The controller ignores the dew point status.
The controller checks which device input is parameterized as a dew point sensor. The status of the
connected dew point sensor is included in control.
The dew point status is received via the group object
The following dependent parameters are shown:
Dew point reached if [controller]
The following dependent group objects are displayed:
Dew point alarm
Channel X
Channel function
Basic-stage cooling [controller]
\ Parameter window
Application parameters
Channel X
\ parameter window
\ Parameter window
Application parameters
Option Controller channel
\
\
all options except Deactivated
Channel X
\ parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B  80
\ Parameter
Channel
Application parameters
Dew point alarm
.
Application parameters
.
.