Double Point Status (Dps) - ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS756567
3.4.8.11.
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual

Double point status (DPS)

Table 3.4.8.11-1 Configurable DPS properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
DPS
Class
Addresses
Indication Index
0...65535
Default: 0
Common
Class
Class 0...3
Default: Class 0
Update Rate
0...65535
Default: 0
Data Class Spe-
cific
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Send All Updates
True
False
Default: False
Send As Inverse
True
Value
False
Default: False
Send As Single
True
Point
False
Default: False
Description
Common data class according to IEC
61850.
Indication index.
Class of ASDU. Data sent from the slave
to the master can be assigned to four
classes. Data in class 1 is sent with higher
priority than data in class 3.
Maximum update rate of signal state
changes between the OPC server and
client in milliseconds. 0 means that the
server sends all the changes to the client.
Object number for indication.
Defines if all changes in value are sent to
the master.
Defines if the value of a message is
inverse.
Defines if a value is sent as single point.
39