3.4.4.
24
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual

Configuring DNP Serial Device

Table 3.4.4-1 Configuring DNP Serial Device properties
Name
Basic
Diagnostics enabled
In Use
Simulation Mode
Event only with changed value
Suppress event on first update
Addresses
Master Station Address
Slave Station Address
Communication Control
Automatic Suspension
Confirmation Timeout
Value or Value range / Default
True
False
Default: False
In use
Not in use
Default: In use
True
False
Default: False
True
False
True
False
0 to 65535
Default: 1
0 to 65535
Default: 1
True
False
Default: True
0 to 600
Default: 10
1MRS756567
Description
Diagnostics Enabled
Controls whether the device
communication is initially in use
or not.
Specifies whether the device is
in simulation mode or not.
If True, then no events are
generated for IED if the new
value and quality are the same
as the current value and qual-
ity.
If True, no is event generated
when the item tag is updated
for the first time.
Station address of the master
station.
Station address of the DNP 3.0
slave station.
When True, consequent
application layer response
timeouts set the station to sus-
pended state and the corres-
ponding process objects are
suspended.
Maximum time in seconds that
the the master station waits for
an application layer confirma-
tion from the master.