COM600 series, Version 5.0
1MRS756567
DNP 3.0 Serial Master (OPC) User's Manual
To add an event poll topic, specify the polling interval in hundreds of millisecond and
the number of events to poll (Value 0 = all events). If you want to poll all events every
1 s, set up as shown in the Add Topic dialog.
SAB600_DNP_Serial_Topic_Generator_EventPoll.png
Figure 3.5-2 Add Event Poll Topic
To add a data poll topic, specify the polling interval in hundreds of millisecond, data
object type and variation, and lower and upper limit of the index range. If you want to
poll 32-bit analog without flag every 1 s, you may set up as shown in the Add Topic
dialog.
SAB600_DNP_Serial_Topic_Generator_DataPoll.png
Figure 3.5-3 Add Data Poll Topic
To modify an existing topic:
1. In Topic Generator Tool, change settings by entering a value or selecting it from
the drop-down list.
2. Click the Save button to save the topic to the configuration.
50