Initialization; Inverter Modes - Omron 3G3RX Quick Start Manual

200 v class three-phase input 0.4 to 55 kw 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

RX Quick Start Guide

3.4 Initialization

Initialize the parameters use the following procedure. Set parameter b084 to "2" and parameter b180 to "1".
Display example
FUNCTION
M1-STOP ALL
Press the Prev. Page or Next Page key
F001
until function mode is displayed. And
Set Frequency (TM)
Press the Set key to enter function
0 .00Hz
mode.
[0.00 – 50.00]
FUNCTION
M1-STOP ALL
With the Prev. Page, Next Page, Up and
b
084
Down keys select parameter b084. Then
Initialize Mode
press the Set key for parameter edition.
00:no
[00 – 04]
FUNCTION
M1-STOP ALL
With the Up and Down keys put the pa-
b084
rameter b084 to 2. Press the set key to
Initialize Mode
store the change
02
:Parameters
[00 – 04]

3.5 Inverter modes

Display code Function name
A044
V/f characteristics
selection
b049
Dual rate selection
d060
Inverter mode
Neither the A044 or the b049 needs a initialization to become effective but some parameters could be changed automatically
when any of these parameters are modified.
This table shows the parameters that change when the dual rating selection is modified, remember that rated currents for heavy
and normal duty are different.
Name
V/f characteristics selection A044
DC injection braking
A054
power
Startup DC injection
A057
braking power
DC injection braking
A059
carrier frequency
Electronic thermal level
b012
Overload limit level
b022
Overload limit level 2
b025
16
Description
Setting range/content
00: VC (Constant torque characteristics)
01: VP (Special reduced torque characteristics)
02: Free V/F (characteristics)
03: SLV (Sensorless vector control)
04: 0SLV (0-Hz sensorless vector control)
05: V2 (Sensor vector control)
00: CT (Constant torque)
150% overload during 60s
01: VT (Variable torque)
120% overload during 60s
IM-CT (Induction motor constant torque)
IM-VT (Induction motor variable torque)
Func.
code
00: VC (Const. torque)
01: VP (Reduced torque)
02: Free V/F
03: SLV (Sensorless vector)
04: 0SLV (0-Hz sensorles)
05: V2 (Sensor vector)
0 to 100(%) 0.4 to 55kW
0 to 80(%) 75 to 132kW
0 to 100(%) 0.4 to 55kW
0 to 80(%) 75 to 132kW
0.5 to 15.0(kHz) 0.4-55kW
0.5 to 10.0(kHz) 75-132kW
(0.20 to 1.00) x Rated current Rated current (A)
(0.20 to 2.00) x Rated current
(A) 04 to 55kW
(0.20 to 1.80) x Rated current
(A) 75 to 132kW
FUNCTION
M1-STOP ALL
b
180
Initialize trigger
00:No action
[00 – 01]
FUNCTION
M1-STOP ALL
b
180
Initialize trigger
01
:Initialize
[00 – 01]
Initial 01 IM-CT
Initial value
00
00
-
HD
00: Const. torque
00: VC (Const. torque)
01: VP (Reduced torque)
02: Free V/F
50(%) 0.4-55kW
0 to 70(%) 0.4 to 55kW
40(%) 75-132kW
0 to 50(%) 75 to 132kW
0(%)
0 to 70(%) 0.4 to 55kW
0 to 50(%) 75 to 132kW
5.0(kHz)0.4-55kW 0.0 to 12.0(kHz) 0.4-55kW
0.5 to 8.0(kHz) 75 - 132kW
(0.20 to 1.00) x Rated current Rated current (A)
1.50 x Rated cur-
(0.20 to 1.50) x Rated current
rent (A)
(A)
With the Prev. Page, Next Page, Up and
Down keys select parameter b180 and
press Set key to edit
With the Up and Down keys put
parameter b180 to 1.
Press the Set key and initialization
process starts
Remarks
Use A244 for second motor
Use A344 for third motor (only
option 0 and 1 available)
Some parameters default and
ranges depends off this setting.
Refer to below table for details
ND
00: Const. torque
50(%) 0.4 to 55kW
40(%) 75 to 132kW
0(%)
3.0(kHz)
1.20 x Rated cur-
rent (A)
RX Quick Start Guide