Wiring Overview; Power Wiring - Omron 3G3RX Quick Start Manual

200 v class three-phase input 0.4 to 55 kw 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for 3G3RX:
Table of Contents

Advertisement

RX Quick Start Guide

2.5 Wiring overview

3-phase 200 V AC
3-phase 400 V AC
To wire the control circuit power
supply and main circuit power
supply separately, be sure to
remove the J51 connector
wire first.
Frequency setting unit
500 to 2 k
Frequency reference auxiliary input (voltage)
*1
L is the common reference for analog input and also for analog output.

2.6 Power wiring

Terminal name
R, S, T
Main power supply input terminals
(L1, L2, L3)
U, V, W
Inverter output terminals
(T1, T2, T3)
PD/+1, P/+
External DC reactor terminal
P/+, RB
Braking resistor connection terminals
Regenerative braking unit connection
P/+, N/-
terminal
Ground terminals
10
Short-circuit
wire
Control circuit
power supply
Multi-function input 1
Multi-function input 2
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 7
Multi-function input 8
Sequence input common
Thermistor
Frequency reference power supply
Frequency reference input (voltage)
Frequency reference input (current)
Frequency reference common
Purpose
Connect the input power supply
Three phase motor connection
Remove the short-circuit bar between terminals "PD/+1" and "P/+", and connect the optional power
factor improvement DC reactor.
Connect optional external braking resistors. (The RB terminal is provided for the inverters with
22KW or lower capacity.)
Connect optional regenerative braking units.
Inverter case ground terminal. Connect this terminal to the ground.
Type-D (200V class), type-C (400V class)
DC reactor
(optional)
PD/+1
P/+
N/-
R/L1
S/L2
T/L3
J51
R
T
Ro
To
CM1
PLC
DC24V
FW
1
2
3
4
5
6
7
8
P24
CM1
TH
H
O
10k
O2
10k
DC10V
OI
100
*1
L
Details
Braking resistor
(optional)
RB
U/T1
V/T2
W/T3
AL1
Relay output *1
AL2
AL0
Common
11
Multi-function output 1
12
Multi-function output 2
13
Multi-function output 3
14
Multi-function output 4
15
Multi-function output 5
CM2
Multi-function output common
SP
SN
RS485 communication
RP
For termination
resistors
SN
Analog monitor output
AM
(voltage output)
Analog monitor output
AMI
(current output)
Digital monitor output
FM
(PWM output)
Option 1
Option 2
RX Quick Start Guide
M