4.0
S
PECIFICATIONS
Table 11
Liebert NXL SCCi Bypass Static Switch and Ebox specifications
Input Parameters
Voltage, VAC, 3-phase, 3-wire or 4-wire
Permissible Input Frequency Range, Hz
Physical Parameters and Standards, in (mm)
Static Bypass Weight, Unpackaged, lb (kg), approx.
Maximum Heat Dissipation, Full Load, BTU/hr (kWH)
Standards and Conformities
Environmental Parameters
Storage Temperature Range, °F (°C)
Operating Temperature Range, °F (°C)
Maximum Altitude Above mean sea level, ft (m)
Input Voltage Range, VAC
Input Frequency, Hz
3
Cooling Air, CFM (m
/s)
Relative Humidity
1600A - 4000A
480V / 575V / 600V
+15% to -20%
1000 (454)
189,000 (55.3)
15,760 (7.4)
UL 1778, 4th Ed.
CSA 22.2 107.3
FCC Part 15, Class A
IEC62040-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6, Level 4, Criteria A
EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3 ISTA Procedure 1H
-13 to 158 (-25 to 70)
32 to 104 (0 to 40) (UPS)
95% or Less Non-Condensing
(Operating and Non-Operating)
4920 (1500) (per IEC 62040/3) - 1% Max kW derate / 328 rise
between 4921-9842 (100m rise between 1500-3000m)
19
Liebert
Specifications
5000A
480V
60
55 to 65
WEEE
®
™
NXL
System Control Cabinet