5 SETTINGS
c) TRIP AND ALARM LEDS
PATH: SETTINGS
PRODUCT SETUP
 TRIP & ALARM LEDS
MESSAGE
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 LED 1
MESSAGE
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
LED Panel 2: user-programmable LEDs 1 through 24
LED Panel 3: user programmable LEDs 25 through 48
For the enhanced faceplate, the LEDs are located as follows.
LED column 2: user-programmable LEDs 1 through 12
LED column 3: user-programmable LEDs 13 through 24
LED column 4: user-programmable LEDs 25 through 36
LED column 5: user-programmable LEDs 37 through 48
Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic™ operands that control the LEDs. If the
"Self-Reset" (the default setting), the LED illumination will track the state of the selected LED operand. If the
ting is "Latched", the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com-
munications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–3: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
PARAMETER
LED 1 operand
SETTING GROUP ACT 1
LED 2 operand
SETTING GROUP ACT 2
LED 3 operand
SETTING GROUP ACT 3
LED 4 operand
SETTING GROUP ACT 4
LED 5 operand
SETTING GROUP ACT 5
LED 6 operand
SETTING GROUP ACT 6
LED 7 operand
Off
LED 8 operand
Off
LED 9 operand
Off
LED 10 operand
Off
LED 11 operand
Off
LED 12 operand
Off
GE Multilin

USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
Off

USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
SETTING
LED 13 operand
LED 14 operand
LED 15 operand
LED 16 operand
LED 17 operand
LED 18 operand
LED 19 operand
LED 20 operand
LED 21 operand
LED 22 operand
LED 23 operand
LED 24 operand
B30 Bus Differential System
5.2 PRODUCT SETUP

TRIP & ALARM LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand

USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic™ operand
Range: Self-Reset, Latched
PARAMETER
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
5
setting is
LED 1 TYPE
set-
LED 1 TYPE
5-47