GE UR Series B30 Instruction Manual page 420

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 51)
ADDR
REGISTER NAME
3D66
Field Latching Output 1 Open
3D67
Field Latching Output 1 Close
3D68
Field Latching Output 1 Events
3D69
Field Latching Output 1 Reserved (2 items)
3D6B
...Repeated for Field Latching Output 2
B
3D76
...Repeated for Field Latching Output 3
3D81
...Repeated for Field Latching Output 4
3D8C
...Repeated for Field Latching Output 5
3D97
...Repeated for Field Latching Output 6
3DA2
...Repeated for Field Latching Output 7
3DAD
...Repeated for Field Latching Output 8
Field Unit Shared Outputs (Read/Write Setting) (16 modules)
3DC0
Field Shared Output 1 ID
3DC6
Field Shared Output 1 Operate
3DC7
Field Shared Output 1 Unit Dest 1
3DC8
Field Shared Output 1 Channel Dest 1
3DC9
Field Shared Output 1 Unit Dest 2
3DCA
Field Shared Output 1 Channel Dest 2
3DCB
Field Shared Output 1 Events
3DCC
...Repeated for Field Shared Output 2
3DD8
...Repeated for Field Shared Output 3
3DE4
...Repeated for Field Shared Output 4
3DF0
...Repeated for Field Shared Output 5
3DFC
...Repeated for Field Shared Output 6
3E08
...Repeated for Field Shared Output 7
3E14
...Repeated for Field Shared Output 8
3E20
...Repeated for Field Shared Output 9
3E2C
...Repeated for Field Shared Output 10
3E38
...Repeated for Field Shared Output 11
3E44
...Repeated for Field Shared Output 12
3E50
...Repeated for Field Shared Output 13
3E5C
...Repeated for Field Shared Output 14
3E68
...Repeated for Field Shared Output 15
3E74
...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 modules)
3E80
Field Unit RTD 1Name
3E86
Field Unit RTD 1 Origin
3E87
Field Unit RTD 1 Type
3E88
...Repeated for Field Unit RTD 2
3E90
...Repeated for Field Unit RTD 3
3E98
...Repeated for Field Unit RTD 4
3EA0
...Repeated for Field Unit RTD 5
3EA8
...Repeated for Field Unit RTD 6
3EB0
...Repeated for Field Unit RTD 7
3EB8
...Repeated for Field Unit RTD 8
Field Unit Transducers (Read/Write Setting) (8 modules)
3ED0
Field Unit Transducer 1 Name
3ED6
Field Unit Transducer 1 Origin
3ED7
Field Unit Transducer 1 Range
3ED8
Field Unit Transducer 1 Min Value
3EDA
Field Unit Transducer 1 Max Value
3EDC
Field Unit Transducer 1 Units
3EDF
...Repeated for Field Unit Transducer 2
3EEE
...Repeated for Field Unit Transducer 3
B-20
RANGE
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 8
1 to 15
0 to 8
1 to 15
0 to 1
0 to 1
0 to 24
0 to 2
0 to 1
0 to 24
0 to 9
-9999.999 to 9999.999
-9999.999 to 9999.999
---
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
---
1
F102
---
1
F001
---
1
F205
---
1
F300
---
1
F256
---
1
F001
---
1
F256
---
1
F001
---
1
F102
---
1
F205
---
1
F253
---
1
F259
0 (100 Ohm Nickel)
---
1
F205
---
1
F253
---
1
F246
---
0.001
F004
---
0.001
F004
---
---
F206
DEFAULT
0
0
1 (Enabled)
0
"SO 1"
0
0 (None)
1
0 (None)
1
1 (Enabled)
"RTD 1"
0 (None)
"TRD 1"
0 (None)
6 (0...20mA)
0
100000
(none)
GE Multilin