Table B–10: MODBUS MEMORY MAP (Sheet 17 of 51)
ADDR
REGISTER NAME
42D6
...Repeated for User-Programmable LED 44
42D8
...Repeated for User-Programmable LED 45
42DA
...Repeated for User-Programmable LED 46
42DC
...Repeated for User-Programmable LED 47
42DE
...Repeated for User-Programmable LED 48
Installation (Read/Write Setting)
43E0
Relay Programmed State
43E1
Relay Name
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
4442
User Programmable Direct Device Off Function
4443
User Programmable Remote Device Off Function
4444
User Programmable Primary Ethernet Fail Function
4445
User Programmable Secondary Ethernet Fail Function
4446
User Programmable Battery Fail Function
4447
User Programmable SNTP Fail Function
4448
User Programmable IRIG-B Fail Function
4449
User Programmable Ethernet Switch Fail Function
444A
Process Bus Failure Operand
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
4481
Phase CT 1 Secondary
4482
Ground CT 1 Primary
4483
Ground CT 1 Secondary
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 modules)
4500
Phase VT 1 Connection
4501
Phase VT 1 Secondary
4502
Phase VT 1 Ratio
4504
Auxiliary VT 1 Connection
4505
Auxiliary VT 1 Secondary
4506
Auxiliary VT 1 Ratio
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
4583
Source 1 Phase CT
4584
Source 1 Ground CT
4585
Source 1 Phase VT
4586
Source 1 Auxiliary VT
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
GE Multilin
RANGE
0 to 1
---
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65535
1 to 65000
0 to 1
1 to 65000
0 to 1
0 to 1
25 to 240
1 to 24000
0 to 6
25 to 240
1 to 24000
0 to 1
0 to 63
0 to 63
0 to 63
0 to 63
25 to 60
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F133
0 (Not Programmed)
---
---
F202
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F300
A
1
F001
---
1
F123
A
1
F001
---
1
F123
---
1
F100
V
0.1
F001
:1
1
F060
---
1
F166
V
0.1
F001
:1
1
F060
---
1
F206
---
1
F400
---
1
F400
---
1
F400
---
1
F400
Hz
1
F001
DEFAULT
B
"Relay-1"
1 (Enabled)
1 (Enabled)
1 (Enabled)
0 (Disabled)
0 (Disabled)
1 (Enabled)
1 (Enabled)
1 (Enabled)
1 (Enabled)
0
1
0 (1 A)
1
0 (1 A)
0 (Wye)
664
1
1 (Vag)
664
1
"SRC 1"
0
0
0
0
60